Motor Sizing Calculator

FREE

Selection & Derating Factors

Advanced
Motor Sizing is a Pro feature
Unlock all professional tools with VerElect Pro
Upgrade to Pro

Load Requirements

Typical: 1.0 (Precise duty), 1.15 (Normal), 1.25 (Heavy duty), 1.5 (Severe duty)

Environmental Factors

Motor Selection

Recommended Motor Size

15.0 kW
15.0 kW / 20.1 HP
Full Load Current
30.5 A
Starting Current (DOL)
198.0 A
Star-Delta Start
66.0 A
~2-2.5x FLA
Soft Starter
91.4 A
~3x FLA
Motor Efficiency
88.0%

Calculation Steps

1. Load power requirement: 10 kW

2. Load power normalized: 10.00 kW

3. Motor power (with service factor 1.15): 10.00 × 1.15 = 11.50 kW

4. Total derating factor: 1.000

5. Derated motor power: 11.50 / 1.000 = 11.50 kW

6. Recommended motor size: 15 kW (standard size)

7. Full Load Current (3-phase): I = P / (√3 × V × η × cosφ)

8. I = 15000 / (1.732 × 380 × 0.88 × 0.85) = 30.47 A

9. Starting Current (DOL): 30.47 × 6.5 = 198.04 A

10. Starting Current (Star-Delta): 198.04 / 3 = 66.01 A

11. Starting Current (Soft Starter): 30.47 × 3.0 = 91.40 A

Motor Sizing Guidelines

Service Factors:
  • 1.0: Precise duty cycle, no overload
  • 1.15: Normal duty, occasional overload
  • 1.25: Heavy duty, frequent overload
  • 1.5+: Severe duty, impact loads
Derating Required:
  • • Temp >40°C: Derate 1% per °C
  • • Altitude >1000m: Derate 3% per 500m
  • • Poor ventilation: Derate 5-10%
  • • Frequent starts: Increase size 25%
Starting Methods:
  • DOL: 6-8× FLC (simple, high inrush)
  • Star-Delta: 2-3× FLC (reduced torque)
  • Soft Starter: 3-4× FLC (smooth start)
  • VFD: 1.5× FLC (best control)